AWG / AMPACITY
Flexible tinned copper · silicone insulation reference build

Wire sizing / 30—0 AWG · copper

AWG to amps chart & calculator

A working reference for flexible, fine-stranded lead wire, from 30 AWG to 0 AWG. Read current capacity by real conductor cross-section in mm², then use the calculator to check a custom strand construction, conductor material, insulation temperature rating, bundle derating and voltage drop on DC or AC.

Current type

Direct current. Voltage drop is counted over the full loop, out and back.

Copper, tinned. 96% IACS, ρ = 0.01823 Ω·mm²/m, ampacity ×0.98 against annealed copper.

Silicone, 200 °C. Conductor rating 200 °C, ampacity ×1.000 against the published silicone data.

Reference table

AWG → copper area → ampacity

Power sizes from 30 AWG through 0 AWG, including the 4 AWG / 25 mm² market-label case. Select any gauge to load a representative 0.08 mm fine-strand construction into the calculator.

17 gauges

Scroll the table sideways for resistance and maximum run →

AWG to amps: copper cross-section in mm², reference ampacity at 60 °C and 200 °C, conductor resistance and the maximum run at 3% voltage drop, for DC or AC
Gauge Nominal copper
mm²
≤3 conductors
60°C / A
1 conductor
free air / A
≤3 conductors
200°C / A
1 conductor
free air / A
Resistance
mΩ/m · DC
Max run
m @3% · 24 V DC
Max load
at 24 V DC
0.051 2.0 A 2.9 A 2.9 A 3.9 A 357 0.5 47 W
0.080 2.9 A 3.9 A 3.9 A 5.9 A 228 0.5 71 W
0.129 3.9 A 4.9 A 4.9 A 6.9 A 141 0.7 94 W
0.205 4.9 A 6.9 A 6.9 A 9.8 A 88.9 0.8 118 W
0.326 4.9 A 6.9 A 10.8 A 14.7 A 55.9 1.3 118 W
0.518 5.9 A 8.8 A 13.7 A 19.6 A 35.2 1.7 141 W
0.823 7.8 A 11.8 A 18.6 A 25.5 A 22.1 2.1 188 W
1.310 10.8 A 14.7 A 23.5 A 33.3 A 13.9 2.4 259 W
2.080 13.7 A 20.6 A 31.4 A 45.1 A 8.76 3.0 329 W
3.310 18.6 A 26.5 A 40.2 A 58.8 A 5.51 3.5 447 W
5.260 25.5 A 35.3 A 52.9 A 79.4 A 3.47 4.1 611 W
8.370 34.3 A 49.0 A 72.5 A 110.7 A 2.18 4.8 823 W
13.30 47.0 A 69.6 A 98.0 A 152.8 A 1.37 5.6 1.13 kW
21.15 60.7 A 93.1 A 128.4 A 205.8 A 0.862 6.9 1.46 kW
33.62 79.4 A 126.4 A 169.5 A 280.2 A 0.542 8.4 1.90 kW
42.41 91.1 A 148.9 A 195.0 A 331.2 A 0.430 9.2 2.19 kW
53.49 109.7 A 163.6 A 219.5 A 341.0 A 0.341 9.6 2.63 kW
Conditions: copper lead wire, 30°C ambient. The 60°C columns are the conservative everyday reference. The 200°C columns are high-temperature conductor limits, not touch-safe or connector-safe operating targets. More than three conductors require further derating. AWG 24–30 rows are indicative for fine-stranded silicone wire and must be checked against the exact cable datasheet. These figures are for direct current.

How to read this AWG to amps chart

Every row pairs an American Wire Gauge size with the nominal copper cross-section it actually contains, in mm², and with four current ratings. The gauge number alone tells you nothing about how much current a wire can carry — the copper area does, and that is why the mm² column sits second, right next to the gauge.

Copper area, not outside diameter

Flexible silicone wire is sold by its outside diameter far more often than by its conductor. A cable advertised as 8 AWG may measure 8 mm across the jacket and hold barely 6 mm² of copper. Size from the strand count and strand diameter on the datasheet, then compare that area against the chart. The calculator above does exactly this arithmetic.

The 60 °C and 200 °C columns

The 60 °C columns are the conservative everyday reference: the conductor stays cool, terminals stay within their own ratings, and there is margin for a hot day. The 200 °C columns are the thermal limit of the silicone insulation, not a design target. A conductor run at its 200 °C limit will melt heat-shrink, discolour terminals and burn skin on contact, so use it only to understand the headroom you have, never as the number you design to.

Maximum load — where the current type really shows

The ampacity columns are in amperes, and amperes are amperes: a conductor does not care whether the heat came from DC or AC. What changes completely is what those amperes are worth. The same 0 AWG conductor at its 109.7 A rating delivers 2.6 kW on a 24 V DC system, 13.2 kW on 120 V single-phase, and 36 kW on 208 V three-phase — a factor of fourteen, from voltage and the √3. On a 230/400 V system the spread is wider still, at twenty-nine.

Read the other way round, that is the number most people actually want: for a given load, the current you must carry is wildly different between DC and AC, and the copper you need follows the current, not the watts. A 3 kW load is 125 A at 24 V DC and 8.3 A at 208 V three-phase.

Resistance and maximum run

The last two columns are the ones the current-type toggle moves most. Resistance is ρ/A per metre, switching to the AC value at your chosen frequency. Maximum run is the longest one-way length that keeps the drop within 3 % while the conductor carries its ≤3 conductor 60 °C current, at the voltage set in the calculator.

That last column is worth staring at. The same 0 AWG conductor is good for 9.6 m on a 24 V DC system and 105 m on 208 V three-phase — a factor of eleven, from voltage and the √3 alone, with the copper completely unchanged. Ampacity is rarely what limits a long run; voltage drop is.

Bundled versus free air

A single conductor hanging in still air sheds heat in every direction. The same conductor in the middle of a loom shares its heat with its neighbours, and all of them run hotter. The ≤3 conductors columns assume a normal cable or small bundle; the free air columns assume one conductor with nothing around it. Anything above three current-carrying conductors needs the grouping factors in the calculator on top.

How the wire gauge calculator works

The calculator starts from the physical construction of the wire rather than from its label, then walks the same four steps an engineer would.

1. Cross-section from strand count

Copper areaA = n × π × d² / 4

n is the number of strands and d is the diameter of one strand in millimetres. A typical 4 AWG silicone lead of 1 650 strands at 0.08 mm works out to 8.29 mm² — well under the 21.15 mm² a real 4 AWG conductor carries, which is exactly the kind of mismatch this page exists to catch.

2. Equivalent AWG

Gauge from areaAWG = 36 − 39 × log(deq / 0.127) / log(92)

The area is converted back to an equivalent solid diameter, then to a gauge number on the AWG scale. The result is usually fractional, which is honest: real stranded wire rarely lands exactly on a gauge.

3. Ambient and grouping derating

Derated ampacityI = Ibase × kambient × kgrouping

Base ampacity comes from your own cross-section, not from whichever row is closest: between two tabulated gauges the current follows a power law in area, I ∝ Ak, with k taken from that pair of rows — 0.5 to 0.7 here, because heat arrives through a section and leaves through a surface. Land exactly on a gauge and you get the published figure back. The ambient factor is interpolated between the published correction points — 60 °C conductors lose capacity quickly above 30 °C, while 200 °C conductors keep working far into the heat. The grouping factor comes from the installation selector, and the two multiply.

4. Voltage drop and wire loss

Direct current, and single-phase ACΔU = 2 × I × R × L × cos φThree-phase AC, line to lineΔU = √3 × I × R × L × cos φ

R is the resistance per metre, ρ/A, with ρ = 0.0175 Ω·mm²/m for copper at 20 °C, and L is the one-way run. Direct current and single-phase AC both travel out and back, so the length counts twice. A three-phase circuit does not: the line-to-line drop carries a √3 instead. Power factor is 1 for DC, which is why the first formula collapses to the familiar 2IRL.

Power lost as heat is I²R per conductor — two conductors for DC and single-phase, three for three-phase. On low-voltage systems this, not ampacity, is usually what forces a bigger conductor: a 12 V circuit allows only 0.36 V of drop at the common 3 % target.

Reactance is left out. For the cross-sections and run lengths this page covers it sits well below the uncertainty in the resistance itself, but on long three-phase runs in conduit it stops being negligible and you should size from the cable's published R and X.

5. Why three-phase derates, and why frequency mostly does not

Two separate things are at work, and they are wildly different in size.

Conductor count is the big one. A three-phase circuit puts three current-carrying conductors in the cable where DC and single-phase put two. Three conductors each dissipating I²R make half again as much heat in the same bundle, so each one has to be rated lower. IEC 60364-5-52 handles this by publishing separate 2 loaded conductors and 3 loaded conductors columns; across its copper tables the ratio averages 0.915, and that is the factor applied to the in-cable columns here. It is a frequency-independent, roughly 9 % cut — the reason 0 AWG reads 109.7 A on DC and 100.4 A on three-phase. The free-air columns describe one isolated conductor, which is the same object in every mode, so they do not move.

Frequency is the small one, at least at mains. Alternating current pushes charge toward the conductor surface, so resistance rises — but in copper at 60 Hz the skin depth is about 8.5 mm, while even a 0 AWG conductor has a radius of only 4.1 mm.

Skin and proximity, IEC 60287-1-1ys = xs⁴ / (192 + 0.8 xs⁴)yp = ys (d/s)² [0.312 (d/s)² + 1.18 / (ys + 0.27)]

Both effects are counted — skin, plus the proximity effect of neighbouring conductors, which dominates once you leave mains frequency. Together they come to 0.40 % at 60 Hz for 0 AWG, 0.06 % at 4 AWG and nothing measurable below that. This is the entire difference between DC and single-phase AC here: both have two loaded conductors, and unarmoured low-voltage wire has no sheath or dielectric losses to add. The table shows a decimal place so you can see it on the gauges where it exists — 0 AWG goes from 109.7 A to 109.5 A — and read as identical where it genuinely is. Ampacity scales as 1/√(1+ys), so it moves by well under a tenth of a percent — far less than the spread between one manufacturer's datasheet and another's. So the frequency term alone would not justify a separate AC column; the conductor count is what does.

It does start to matter higher up. At 400 Hz — aircraft and some drive systems — 0 AWG picks up 17 %, which is why the calculator takes a frequency rather than assuming mains. The published fit holds to xs ≤ 2.8, roughly 1 kHz on the largest gauge here; above that the calculator flags its own result as indicative.

Conductor materials

AWG is a geometric size, so the cross-section in the table is the same whatever the metal is. What changes is how much current that cross-section can carry and how much voltage it drops. Both follow from one number — conductivity, quoted on the IACS scale where annealed copper is 100 %.

Ampacity against copperI / ICu = √(σ / σCu)Resistance against copperR / RCu = σCu / σ

Identical geometry and an identical permitted temperature rise mean I²R is fixed, so current goes as the inverse square root of resistivity. That is not a rule of thumb: against NEC 310.16 the aluminium-to-copper ratio averages 0.774 from 6 AWG to 4/0, where √0.612 predicts 0.782.

What the selector offers

Copper
100% IACS · ×1.000
Silver
105% IACS · ×1.025
Tinned copper
96% IACS · ×0.980
Nickel-plated
95% IACS · ×0.975
Aluminium 1350
61.2% IACS · ×0.782
Alloy 8000
61% IACS · ×0.781
Copper-clad alu
61.5% IACS · ×0.784
Copper-clad steel
30% IACS · ×0.548

Anything else goes in as a custom % IACS, which is the honest way to handle a datasheet that quotes its own figure.

Plated coppers

Plating is about the environment, not conduction. Tin resists corrosion and keeps solder wetting; nickel survives past 200 °C where tin has long melted; silver is for RF, where current rides the surface. The penalty is small and depends on how thick the coating is relative to the strand: on a 0.08 mm strand a micron of tin occupies roughly 5 % of the area and conducts at 15 % of copper, which is where the 96 % figure comes from. On thicker strands it is less. Silver plating does not change DC resistance measurably, since the bulk is still copper.

Aluminium, and what it costs you

Aluminium carries about 78 % of copper's current at the same size, so matching a copper conductor takes 1.64× the area — roughly two AWG sizes up. It is still worth it on long runs, because it is around a third of the weight for the same conductance and much cheaper.

The catch is never the metal, it is the joint. Aluminium creeps under clamping pressure, so a terminal that was tight last year may not be now; it grows an insulating oxide the moment it meets air; and it expands about 40 % more than copper with temperature, working itself loose through every heating cycle. Aluminium branch circuits earned their reputation in the 1960s and 70s for exactly this. Use terminals listed for aluminium, apply anti-oxidant compound, torque to the figure on the connector, and never put bare aluminium against bare copper in a damp place — the galvanic pair eats the aluminium.

Fine-stranded silicone wire, which is what this page is mostly about, is not made in aluminium: it does not survive the flex cycles.

Copper-clad conductors

Copper-clad aluminium is aluminium with a copper skin, typically 10 % by volume. It terminates like copper and conducts like aluminium, which is a reasonable trade — the problem is that it is frequently sold as copper. Strip a sample: the core is silver-coloured. Copper-clad steel is a different animal at 30 % IACS, made for mechanical strength and RF skin conduction, not for carrying power; a magnet identifies it instantly.

One caveat on temperature

Every figure here is at 20 °C. A conductor actually running at 60 °C has around 16 % more resistance, and aluminium's temperature coefficient (0.00403/K) is slightly worse than copper's (0.00393/K). For voltage drop on a hot circuit, add that margin yourself — the calculator does not, because it would need a conductor temperature rather than an ambient one.

Insulation

Insulation contributes one thing to ampacity: how hot it will let the conductor get. Copper does not care — it is happy at 400 °C. The plastic around it decides where you have to stop, and that single number moves the high-temperature column of the table.

Ampacity at a different ratingI / I200 = √( (T−30) / (1 + α(T−20)) ) ÷ √( 170 / (1 + α·180) )

Heat leaves the conductor in proportion to ΔT while heat arrives as I²R, and R itself climbs with temperature — which is why the gain from a hotter rating is less than it first looks. Against NEC 310.16 this predicts the 90 °C to 60 °C ratio as 1.347 where the published columns give 1.333 to 1.360 for 10 AWG and larger. Silicone at 200 °C is the reference at exactly 1.000, so selecting it reproduces the published data untouched.

What the selector offers

PVC
70 °C · ×0.579
PVC/nylon THHN
90 °C · ×0.687
XLPE / EPR
90 °C · ×0.687
PVC, heat-resistant
105 °C · ×0.751
ETFE (Tefzel)
150 °C · ×0.893
Silicone
180 °C · ×0.962
Silicone, FEP
200 °C · ×1.000
PTFE / PFA
260 °C · ×1.090

The rule that catches people out

The whole circuit runs at the temperature of its weakest part, and that is almost never the wire. A breaker terminal listed for 75 °C caps the whole run at 75 °C no matter what the insulation says — NEC 110.14(C) makes this explicit, and most equipment under 100 A is listed at 60 °C. Buying 200 °C silicone and sizing from its 200 °C column, then landing it in a 75 °C lug, is how connections cook. This is exactly why the conservative 60 °C column stays fixed in this table regardless of what you select: for most real installations it is the number that governs.

The high-temperature rating buys you margin in a hot enclosure, survival next to an exhaust or a heater, and the ability to run at full current when the ambient is already 80 °C. It does not license you to push more current through the same terminals.

Choosing between them

PVC is cheap, tough against abrasion and stiff in the cold; it softens where it is hot and gives off hydrogen chloride in a fire, which is why LSZH compounds replace it in tunnels and ships. XLPE is PVC's crosslinked cousin: same price bracket, better heat, does not melt and flow. Silicone is the most flexible thing on the list by a wide margin and survives 200 °C, but it tears and abrades easily, so it wants a sleeve wherever it can rub. PTFE and PFA are the best electrically and thermally and shrug off almost every solvent, at several times the price and with noticeably less flexibility. ETFE is the compromise the aerospace world settled on: thin wall, tough, 150 °C.

Two things this does not model

Wall thickness. A thick jacket is a thermal blanket, so two 90 °C cables of different construction do not carry the same current. Datasheets rarely publish thickness in a comparable way, so only the rating is used here.

Voltage rating, which is a separate property entirely. 600 V, 1 kV and 3 kV versions of the same insulation share a temperature rating and differ only in wall. Check it separately — nothing on this page tells you whether the insulation will hold your voltage.

AWG to mm² at a glance

Nominal copper cross-sections per ASTM B258, with the nearest metric cable size the market actually sells against each one.

0 AWG
53.49 mm² · ≈ 50 mm²
2 AWG
33.62 mm² · ≈ 35 mm²
4 AWG
21.15 mm² · ≈ 25 mm²
6 AWG
13.30 mm² · ≈ 16 mm²
8 AWG
8.37 mm² · ≈ 10 mm²
10 AWG
5.26 mm² · ≈ 6 mm²
12 AWG
3.31 mm² · ≈ 4 mm²
14 AWG
2.08 mm² · ≈ 2.5 mm²
16 AWG
1.31 mm² · ≈ 1.5 mm²
18 AWG
0.823 mm² · ≈ 1 mm²
20 AWG
0.518 mm² · ≈ 0.5 mm²
22 AWG
0.326 mm² · ≈ 0.35 mm²

The right-hand figure is the size a supplier will usually quote. It is almost always larger than the true AWG area, so a metric cable labelled as an AWG equivalent is safe on ampacity and misleading on price per millimetre of copper.

Frequently asked questions

How many amps can each AWG wire size carry?

For tinned copper conductors at 30 °C ambient, the conservative 60 °C reference in the chart above gives roughly 7.8 A for 18 AWG, 13.7 A for 14 AWG, 25.5 A for 10 AWG, 34.3 A for 8 AWG, 60.7 A for 4 AWG and 109.7 A for 0 AWG with up to three current-carrying conductors in a cable. A single conductor in free air runs cooler and carries more. High-temperature silicone wire rated to 200 °C carries roughly twice the conservative figure, but only if every terminal, fuse and connector in the circuit is rated for that temperature too.

What is the difference between the 60 °C and 200 °C columns?

Both describe the same copper. The difference is how hot you allow the conductor to get. The 60 °C columns are the everyday design baseline: the wire stays touch-safe and the insulation, terminals and adjacent materials are comfortable. The 200 °C columns are the thermal limit of the silicone insulation itself — the current at which the conductor reaches 200 °C. Treat the second number as a ceiling for short, well-ventilated runs, not as a design target.

How do I convert AWG to mm²?

AWG is a logarithmic scale, so there is a closed formula rather than a simple ratio. The conductor diameter in millimetres is d = 0.127 × 92(36−AWG)/39, and the cross-section is A = π d²/4. In practice, every three AWG steps roughly double the copper area, and six steps roughly double the diameter. The mm² column in the chart above already carries the ASTM B258 nominal values, so you can read the conversion straight off the table.

Why is 25 mm² wire sold as 4 AWG?

Because it is a marketing label, not a measurement. True 4 AWG is 21.15 mm² of copper. Sellers of flexible silicone wire frequently round up to the nearest metric size, or quote the outside diameter over the insulation instead of the conductor. Always size from the strand count and strand diameter on the datasheet — that is what the calculator on this page asks for — and treat any headline mm² figure as unverified until it matches.

Does a higher strand count increase ampacity?

Not by itself. Ampacity follows the total copper cross-section, so 1 650 strands of 0.08 mm carry the same current as a solid conductor of the same area. What fine stranding buys you is flexibility, vibration and flex-cycle life, and easier routing in tight enclosures. At DC and mains frequencies the skin effect is negligible at these sizes, so stranding gives no measurable current bonus.

How do I calculate DC voltage drop?

Voltage drop is the load current times the resistance of the full circuit — out and back. With copper resistivity ρ = 0.0175 Ω·mm²/m, the drop is ΔU = I × ρ × 2L / A, where L is the one-way run length. Most low-voltage DC systems aim to keep the drop under 3 % of system voltage; on a 12 V circuit that is only 0.36 V, which is why long 12 V runs are usually sized by voltage drop rather than by ampacity.

How much should I derate for bundled conductors?

Bundling traps heat, so every conductor in the group carries less. Common factors are 80 % for 4–6 current-carrying conductors, 70 % for 7–9, 50 % for 10–20, 45 % for 21–30, 40 % for 31–40 and 35 % beyond that. Ambient temperature derates on top of grouping, and the two multiply. Conductors that never carry current at the same time, and neutrals in a balanced circuit, usually do not count towards the group.

Can I use this chart for aluminium wire?

Yes — switch the conductor material and every column recalculates. Aluminium at 61.2 % IACS carries about 78 % of copper's current at the same cross-section, because ampacity follows the square root of conductivity. Matching a copper conductor therefore takes 1.64 times the area, roughly two AWG sizes up. The arithmetic is the easy part: aluminium creeps under clamping pressure, oxidises on contact with air and expands more than copper when hot, so it needs terminals listed for aluminium, anti-oxidant compound and a torque wrench. Copper-clad aluminium behaves the same electrically while terminating like copper, and copper-clad steel at 30 % IACS is for strength and RF, not for power.

Does the ampacity change between DC and AC?

Not meaningfully at mains frequency. Alternating current crowds toward the conductor surface, but the skin depth in copper is about 9.4 mm at 50 Hz and 8.5 mm at 60 Hz, while a 0 AWG conductor has a radius of just 4.1 mm. By IEC 60287 the resistance rise works out at 0.08 % for 0 AWG and under 0.01 % below 4 AWG, so the same table serves DC, single-phase and three-phase. What the current type really changes is the voltage drop: two conductors out and back for DC and single-phase, √3 line-to-line for three-phase, with the power factor on top. Skin effect only becomes worth counting in the hundreds of hertz, which is why the calculator asks for a frequency.

Is this chart the same as NEC or IEC ampacity?

No. This is a reference for flexible, fine-stranded tinned copper lead wire with silicone insulation, of the kind used in equipment wiring, battery leads, robotics and RC. Building installations are governed by NEC 310 tables in North America and IEC 60364-5-52 in Europe, which assume different insulation, installation methods and correction factors. Use those codes for fixed wiring, and use this chart for equipment and appliance wiring.

Read the source, or fix it

This page is open source. The table data, both translations, the calculator and this text are all produced by one generator, which is why the English and Ukrainian versions cannot drift apart.

  • src/build.php — the ampacity table, the copy, the FAQ and the JSON-LD
  • src/template.html — the page shell and the calculator
  • src/test.js — checks that run the calculator against the built pages

Found a wrong number, or want a gauge added? Open an issue or send a pull request at github.com/66Ton99/homepage. Corrections backed by a datasheet or a standard are especially welcome — the AWG 24–30 rows are the shakiest, since they are indicative for fine-stranded silicone wire rather than taken from a single authoritative table.